Siemens tipidagi AC kontaktor J3TF
Spetsifikatsiya
Turi | J3TF-9/12 | J3TF-16/22 | J3TF-32 | J3TF-45/63 | J3TF-75/85 | J3TF-110/140 | J3TF-170/205 | J3TF-250/300 | J3TF-400/475 | |
Mexanik Chidamlilik (X106) | 10 | 10 | 10 | 8 | 8 | 8 | 8 | 8 | 8 | |
An'anaviy termal oqim (A) | 20 | 30 | 45 | 80 | 100 | 160 | 210 | 300 | 400/550 | |
Nominal izolyatsiya kuchlanish (V) | 660 | 660 | 660 | 1000 | 1000 | 1000 | 1000 | 1000 | 1000 | |
Nominal ishlash joriy (A) | AC-3 | 9/12 | 16/22 | 32 | 45/63 | 75/85 | 110/140 | 170/205 | 250/300 | 400/475 |
AC-4 | 3.3/4.3 | 7,7/8,5 | 15.6 | 24/28 | 34/42 | 54/68 | 75/96 | 110/125 | 150 | |
Boshqariladigan dvigatelning quvvati (KVt) AC-3 | 380V | 4/5,5 | 7,5/11 | 15 | 22/30 | 37/45 | 55/75 | 90/110 | 132/160 | 200/250 |
660V | 5,5/7,5 | 11 | 23 | 39/55 | 67 | 100 | 156 | 235 | 375 | |
Boshqariladigan dvigatelning quvvati (KVt) AC-4 | 380V | 1,4/1,9 | 3,5/4 | 7.5 | 12/14 | 17/21 | 27/35 | 38/50 | 58/66 | 81 |
660V | 2.4/3.3 | 6/6.6 | 13 | 20,8/24 | 29,5/36 | 46,9/60 | 66/86 | 100/114 | 140 | |
Operatsion chastotasi (I/soat) | AC-3 | 1000 | 750 | 750 | 1200/1000 | 1000/850 | 1000/750 | 700/500 | 700/500 | 500/420 |
AC-4 | 250 | 250 | 250 | 400/300 | 300/250 | 300/200 | 200/130 | 200/130 | 150 | |
Elektr chidamlilik (X106) | AC-3 | 1.2 | 1.2 | 1.2 | 1.2 | 1.2 | 1.2 | 1.2 | 1.2 | 1.2 |
AC-4 | 0,2 | 0,2 | 0,2 | 0,2 | 0,2 | 0,2 | 0,2 | 0,2 | 0,2 | |
Ishlash kuchlanishi rulon diapazoni | (0,8-1,1)Ue | |||||||||
Quvvat lasan iste'moli | O'ziga jalb qilish (VA) | 10 | 10 | 12.1 | 17 | 32 | 39 | 58 | 84 | 115 |
Boshlanmoqda (VA) | 68 | 69 | 101 | 183 | 330 | 550 | 910 | 1430 | 2450 | |
Yordamchi kontaktlarning nominal izolyatsiya kuchlanishi (V) | 690 | 690 | 690 | 690 | 690 | 690 | 690 | 690 | 690 | 690 |
Yordamchi kontaktlarning an'anaviy termal oqimi (A) | 10 | 10 | 10 | 10 | 10 | 10 | 10 | 10 | 10 | 10 |
Yordamchi kontaktlarning nominal ish oqimi (A) | AC15 380/220 | 6/10 | 6/10 | 4/6 | 4/6 | 4/6 | 4/6 | 4/6 | 4/6 | 4/6 |
DC13 220v | 0,45 | 0,45 | 0,45 | 0,45 | 0,45 | 0,45 | 0,45 | 0,45 | 0,45 | |
Nominal kuchlanish nazoratdan lasan (V) | 50 Gts | 24 36 48 110 127 220 380 va boshqalar | ||||||||
60 Gts | 24 110 220 440 va boshqalar |
Ilova stsenariylari:
Odatda poldagi tarqatish qutisiga, kompyuter markaziga, telekommunikatsiya xonasiga, liftni boshqarish xonasiga, kabel televideniesiga, bino boshqaruv xonasiga, o't o'chirish markaziga, sanoat avtomatik boshqaruv zonasiga, shifoxona operatsiya xonasiga, monitoring xonasiga va elektron tibbiy asbob-uskunalar bilan tarqatish qutisiga o'rnatiladi. .
Xabaringizni shu yerga yozing va bizga yuboring