Siemens tipidagi AC kontaktor J3TF

Qisqa Tasvir:

J3TF seriyali AC kontaktor chastotasi 50/60Hz, nominal izolyatsiyalash kuchlanishi 1000V gacha, nominal ish oqimi 9-475A AC-3 burchi ostida mos keladi.U asosan uzoq masofadagi elektr zanjirini yaratish/uzish, tez-tez ishga tushirish/to'xtatish va magnit motor starterini yaratish uchun termal o'rni bilan ishlatiladi.Mahsulot IEC60947-4-1 standartiga mos keladi.


Mahsulot detali

Batafsil tavsif

Mahsulot teglari

Spetsifikatsiya

Turi J3TF-9/12 J3TF-16/22 J3TF-32 J3TF-45/63 J3TF-75/85 J3TF-110/140 J3TF-170/205 J3TF-250/300 J3TF-400/475
Mexanik
Chidamlilik (X106)
10 10 10 8 8 8 8 8 8
An'anaviy
termal oqim (A)
20 30 45 80 100 160 210 300 400/550
Nominal izolyatsiya
kuchlanish (V)
660 660 660 1000 1000 1000 1000 1000 1000
Nominal ishlash
joriy (A)
AC-3 9/12 16/22 32 45/63 75/85 110/140 170/205 250/300 400/475
AC-4 3.3/4.3 7,7/8,5 15.6 24/28 34/42 54/68 75/96 110/125 150
Boshqariladigan dvigatelning quvvati (KVt) AC-3 380V 4/5,5 7,5/11 15 22/30 37/45 55/75 90/110 132/160 200/250
660V 5,5/7,5 11 23 39/55 67 100 156 235 375
Boshqariladigan dvigatelning quvvati (KVt) AC-4 380V 1,4/1,9 3,5/4 7.5 12/14 17/21 27/35 38/50 58/66 81
660V 2.4/3.3 6/6.6 13 20,8/24 29,5/36 46,9/60 66/86 100/114 140
Operatsion chastotasi
(I/soat)
AC-3 1000 750 750 1200/1000 1000/850 1000/750 700/500 700/500 500/420
AC-4 250 250 250 400/300 300/250 300/200 200/130 200/130 150
Elektr
chidamlilik
(X106)
AC-3 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2
AC-4 0,2 0,2 0,2 0,2 0,2 0,2 0,2 0,2 0,2
Ishlash kuchlanishi
rulon diapazoni
(0,8-1,1)Ue
Quvvat
lasan iste'moli
O'ziga jalb qilish
(VA)
10 10 12.1 17 32 39 58 84 115
Boshlanmoqda
(VA)
68 69 101 183 330 550 910 1430 2450
Yordamchi kontaktlarning nominal izolyatsiya kuchlanishi (V) 690 690 690 690 690 690 690 690 690 690
Yordamchi kontaktlarning an'anaviy termal oqimi (A) 10 10 10 10 10 10 10 10 10 10
Yordamchi kontaktlarning nominal ish oqimi (A) AC15
380/220
6/10 6/10 4/6 4/6 4/6 4/6 4/6 4/6 4/6
DC13
220v
0,45 0,45 0,45 0,45 0,45 0,45 0,45 0,45 0,45
Nominal kuchlanish
nazoratdan
lasan (V)
50 Gts 24 36 48 110 127 220 380 va boshqalar
60 Gts 24 110 220 440 va boshqalar

  • Oldingi:
  • Keyingisi:

  • Ilova stsenariylari:
    Odatda poldagi tarqatish qutisiga, kompyuter markaziga, telekommunikatsiya xonasiga, liftni boshqarish xonasiga, kabel televideniesiga, bino boshqaruv xonasiga, o't o'chirish markaziga, sanoat avtomatik boshqaruv zonasiga, shifoxona operatsiya xonasiga, monitoring xonasiga va elektron tibbiy asbob-uskunalar bilan tarqatish qutisiga o'rnatiladi. .